BS EN 50525-2-31:2011 pdf free

05-07-2021 comment

BS EN 50525-2-31:2011 pdf free.Electric cables -Low voltageenergy cables of rated voltagesup to and including 450/750 V(Uo/U) Cables for general applications-Single core non-sheathed cables withthermoplastic PVC insulation.
BS EN 50525-2-31 EN 50525-2-31 applies to non-sheathed single core cables insulated with thermoplastic(PvC) insulation.The cables are of rated voltages Uo/U up to and including 450/750 V.The cables are intended for fixed wiring applications.
NOTE1 Cables rated 450/750 V may be used at 600/1 0o0 v when this cable is used in fixed installations withmechanical protection,within switchgear and control gear – see HD 516.
The maximum conductor operating temperatures for the cables in this standard are 70 C(V types) and 9o c (v2 types).
NOTE 2 HD 516 contains extensive guidance on the safe use of cables in this standard.
This EN 50525-2-31 should be read in conjunction with EN 50525-1, which specifies generalrequirements.
The following referenced documents are indispensable for the application of this document.For dated references, only the edition cited applies.For undated references, the latest editionof the referenced document (including any amendments) applies.
NOTEOne or more references to the standards below are in respect of a specific sub-division of that standard,for instance a clause, a table, a class or a type. Cross-references to these standards are undated and, at all times,the latest version applies.
The insulation shall be polyvinyl chloride compound of Type Tl 1 to EN 50363-3 appliedaround the conductor.
The cable shall be marked with the CENELEC code H07V-U for cables with class 1conductor,or HO7V-R for cables with class 2 conductor. The marking shall comply withClause 6 of EN 50525-1.
Each cable shall comply with the appropriate requirements given in EN 50525-1,and theparticular requirements of this Part.Testing shall be in accordance with Annex A, and the relevant tests indicated in column 6.
The dimensions of the cables shall conform to Table B.1 for the relevant size.The cable shall be marked with the CENELEC code HO7V-K. The marking shall comply withClause 6 of EN 50525-1.
Each cable shall comply with the appropriate requirements given in EN 50525-1, and theparticular requirements of this Part.Testing shall be in accordance with Annex A, and the relevant tests indicated in column 7.
The dimensions of the cables shall conform to Table B.2 for the relevant size.BS EN 50525-2-31 pdf download.

Download infomation Go to download
Note: Can you help me share this website on your Facebook or others? Many thanks!
BS ISO 7425-1:2021 pdf free Free BS Standards

BS ISO 7425-1:2021 pdf free

BS ISO 7425-1:2021 pdf free.Hydraulic fluid power cylinders一Dimensions and tolerances of housings for elastomer- energized, plastic-faced seals Part 1: Piston seal housings. 5.2 Axial length For axial lengths for the nominal piston diameters, see Iable3. If the...
Get More
BS EN ISO 8407-2021 pdf free download Free BS Standards

BS EN ISO 8407-2021 pdf free download

BS EN ISO 8407-2021 pdf free download.Corrosion of metals and alloys一Removal of corrosion products from corrosion test specimens. 4.1.6 The true mass of the specimen, after removal of the corrosion products, will be a value between the...
Get More

LEAVE A REPLY

Anonymous netizen Fill in information